Control tier for foxess_h3_smart (1K5 / H3-Smart): proposal and mapped control surface #70

Description

@Leitet

Follow-up to #68 / #69 (read-only foxess_h3_smart). Opening this to take the control question to the team rather than assuming an answer.

Why

A live FTW site runs a 1K5-HI-10-V1 as its only DER. Telemetry works, but FTW's planner requires a controllable battery — the read-only driver keeps the control pool empty, so the planner is (correctly) skipped and the site runs on the inverter's internal logic. Every FoxESS H3-Smart-map site will sit in this state until a control tier exists.

What the register map offers

From the same source the read-only driver was built against (nathanmarlor/foxess_modbus, Inv.H3_SMART profile), all holding registers, mapped from source but not yet written to on hardware:

  • 46607 / 46608 — max charge / max discharge current, 0.1 A steps
  • 46609 / 46610 / 46611 — min SoC, max SoC, min SoC on-grid
  • 46616–46617 — export power limit (W, i32 pair)
  • 46501–46502 — import power limit (W, i32 pair)
  • 49203 — work mode
  • foxess_modbus additionally implements a "remote control" force-charge/discharge path with power setpoints; whether and how it applies to the H3-Smart map needs verification before it can be the dispatch lever

A useful v1 lever for FTW's driver_command("battery", power_w) is probably the narrowest one that works: the charge/discharge current window (with the SoC window as bounds), leaving work-mode writes and the remote-control path as later stages once HIL evidence exists.

What policy requires (as I read AGENTS.md / CONTRIBUTING.md)

  • Control is a separate change, never bundled with telemetry review; community-tier review alone is insufficient.
  • Safe default mode, bounded leases, structured results, HIL acceptance per target host.
  • The signed public channel is read-only, so this ships as a signed control package (com.sourceful.driver.* with exact version + artifact SHA pinned in FTW's driver control block).

Questions for the team

  1. Is FoxESS control wanted on the roadmap now, or parked until there are more H3-Smart-map sites?
  2. What is the current state of the control-package pipeline — has any driver shipped through it yet, and is there a reference to follow?
  3. Is the current-window lever an acceptable v1 dispatch mechanism, or is the remote-control path a hard requirement for planner-grade control?

Offer

A 1K5-HI-10-V1 on a live site (with its owner operating it) is available as the HIL rig — the same unit that validated the read-only driver's telemetry against V×A cross-checks and grid CT balance.

🤖 Drafted with Claude Code

Activity

  1. Leitet commented on Aug 3, 2026

    @Leitet
    MemberAuthor

    Hardware update from the 1K5-HI-10-V1: remote control works, and the register recipe is now confirmed on real hardware — with one trap that explains why naive attempts fail silently.

    • The block is exactly foxess_modbus's H3_SMART remote-control spec: 46001 enable (value 1 works — no magic values needed), 46002 timeout seconds, 46003/46004 i32 setpoint, discharge-positive. Work mode can stay Self-use; 44000 legacy block is absent (reads time out).
    • The trap: the manager (ESP32 front-end) and the master sample asynchronously. Writes land instantly and read back correctly, but the master acts on the remote-control state on a slow cycle — a 15 s timeout expired before the master ever looked, so the session was accepted, stored, verified by read-back… and did nothing, with zero error surface. With timeout = 60 s (refreshed every 5 s poll) the inverter executes setpoints and a closed control loop converges (grid-zero tracking observed live: targets ≈ −630 W, battery following, import driven 413 → 150 W).
    • The FoxESS app's own scheduler Force Charge/Discharge uses these same registers (observed live: enable 1, timeout = period length 2520 s, setpoint 500) — so vendor-side scheduling and a local controller contend for one register block, last-writer-wins. A control driver should document that operators must disable app schedule periods.
    • Safety posture that worked in practice: fallback work mode Self-use, vendor timeout 60 s as the inverter-side dead-man, plus a driver-side 60 s command lease so a silent EMS releases control rather than refreshing a stale setpoint; explicit release in driver_default_mode. Charge-into-full refused at driver level (the inverter ignores Max SoC under remote control, per foxess_modbus).

    This is running as a local operator-risk build per Fredrik's guidance; happy to shape it into the signed control package when the pipeline questions above have answers.

    🤖 From the HIL session on the offered rig.

  2. Leitet commented on Aug 3, 2026

    @Leitet
    MemberAuthor

    The implementation behind the recipe above is now reviewable as draft PR #71 — running live on the 1K5 site as a local override, explicitly not mergeable until the pipeline questions here have answers.

Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment

Metadata

Metadata

Assignees

No one assigned

    Labels

    No labels
    No labels

    Type

    No type

    Projects

    No projects

      Milestone

      No milestone

      Relationships

      None yet

      Development

      No branches or pull requests

      Issue actions